Use the LimitAlarmDvStbySeq_REAL instruction to output upper/lower deviation alarms with a
standby sequence for the deviation between the set point and the process temperature.
5
Perform an output as a safety measure if an error occurs in the LimitAlarmDvStbySeq_REAL
instruction or if an upper/lower deviation alarm occurs.
6
Perform temperature control with the PIDAT instruction.
7
Use the TimeProportionalOut instruction to output the manipulated variable as a time-propor-
tional value to the heating device.
 Operation of Upper/Lower Limit Alarms and Upper/Lower Deviation Alarms
with Standby Sequence
Upper deviation temperature = 50°C
Lower deviation temperature = 50°C
Error in LimitAlarm_REAL instruction
Error in LimitAlarmDv_REAL instruction
Output for safety measure
for LimitAlarm_REAL instruction
Output for safety measure for
LimitAlarmDvStbySeq_REAL instruction
2-758
Process temperature (°C)
Upper limit of temperature 200
195
150
147
Set point 100
53
50
5
Lower limit of temperature 0
TRUE
Upper limit alarm
FALSE
TRUE
Lower limit alarm
FALSE
TRUE
Upper deviation alarm
FALSE
TRUE
Lower deviation alarm
FALSE
Enabled
Standby sequence
Disabled
Yes
No
Yes
No
TRUE
FALSE
TRUE
FALSE
Hysteresis of upper/
Hysteresis of upper/
lower limit alarm = 5°C
lower deviation alarm = 3°C

NY-series Instructions Reference Manual (W560)