2 Instruction Descriptions
• An error occurs if the value of AIn, CtlPrd, MinPlsWidth, or Delay is outside of the valid range.
Error changes to TRUE and DOut changes to FALSE. If the value of AIn exceeds the valid range,
the operation of DOut will be as shown below depending on when the error is reset.
• If the error is reset after the point where DOut changes to TRUE, the time-proportional output for
DOut is restarted from the next control period.
TRUE
DOut
FALSE
TRUE
Error
FALSE
AIn
(%)
101
60
• If the error is reset before the point where DOut changes to TRUE, the time-proportional output for
DOut is restarted in the control period in which the error was reset.
Delay = 20%
TRUE
DOut
FALSE
Error
AIn
(%)
101
60
Version Information
A CPU Unit with unit version 1.02 or later and Sysmac Studio version 1.03 or higher are required
to use this instruction.
Sample Programming
This sample performs temperature control for four points with upper/lower limit alarms and upper/lower
deviation alarms. PID control is performed. The manipulated variables of PID control are converted to
time-proportional output values that are output to heating devices.
Process temperature
Set point
2-732
CtlPrd = 1 s
600 ms
The value of AIn is
outside of the valid range,
so Error is TRUE.
Value updated.
Value updated.
CtlPrd = 1 s
200 ms
600 ms
The value of AIn is outside of the
valid range, so Error is TRUE.
Value updated.
Value updated.
PID
control
CtlPrd = 1 s
The value of AIn is inside of
Time-proportional output is restarted
the valid range, so Error is
from the next control period after the
FALSE.
error is reset.
Value updated.
CtlPrd = 1 s
200 ms
600 ms
The value of AIn is inside of the
valid range, so Error is FALSE.
Value updated.
Time
Conversion to
time-proportional output

NY-series Instructions Reference Manual (W560)

CtlPrd = 1 s
600 ms
Time
Time-proportional output is
restarted in the control period in
which the error was reset.
Heating device