2 Instruction Descriptions
Task period = 60 ms and SampTime = 100 ms
The task period is less than SampTime, so DIP processing is not executed every period.
Task period
PIDAT
60 ms
PID processing
executed.
Time
Not executed because elapsed time
(60 ms) < 100 ms.
Executed because elapsed time (60 + 60 ms = 120 ms) > 100 ms.
The remaining 20 ms is carried over.
Timing Charts
Timing charts for the instruction variables are provided below for different situations.
 Autotuning Executed during Automatic Operation
TRUE
Run
FALSE
TRUE
StartAT
FALSE
TRUE
ATBusy
FALSE
TRUE
ATDone
FALSE
StopMV
2-678
Task period
Task period
PIDAT
PIDAT
60 ms
PID processing
PID processing
executed.
not executed.
PV
SP
MV
PID processing
processing
Autotuning
PID constants updated for
results of autotuning.
Task period
PIDAT
60 ms
60 ms
PID processing
not executed.
Executed because elapsed time
(80 + 60 ms = 140 ms) > 100 ms.
The remaining 40 ms is carried over.
Not executed because elapsed time
(20 + 60 ms = 80 ms) < 100 ms.
Time
Time
PID
MV set to StopMV.

NY-series Instructions Reference Manual (W560)

Task period
PIDAT
PID processing
executed.