Ny-Series Instructions Reference Manual (W560 - Omron NY532-5400 Reference Manual

Ny-series
Hide thumbs Also See for NY532-5400:
Table of Contents

Advertisement

Internal
Variable
Variables
TimeInfo
ACSP_Done
Run
ManCtl
StartAT
PreStartAT
OprSetParams
InitSetParams
ManMV
ATBusy
PID_ErrorID
PID_Error
MV
ATDone
TPO_Error
PIDbank
TPO_Enable
MinPlsWidth
Delay
ACSP
PID
TPO
External
Variables
N1_Ch1_Measured_Value_REAL
N2_Output_Bit_00

NY-series Instructions Reference Manual (W560)

Data type
_sAC_STEP_TIME
BOOL
BOOL
BOOL
BOOL
BOOL
_sOPR_SET
_PARAMS
_sINIT_SET
_PARAMS
REAL
BOOL
WORD
BOOL
REAL
BOOL
BOOL
ARRAY[0..7] OF
sPID_BANK
BOOL
REAL
REAL
AC_StepProgram
PIDAT
TimeProportionalOut
Data
Variable
type
REAL
BOOL
2 Instruction Descriptions
Initial value
(ProgramTime:=T#0s,
ElapseTime:=T#0s,
ProgressTime:=T#0s,
LeftTime:=T#0s,
StepProgressTime:=T#0s,
StepLeftTime:=T#0s)
FALSE
FALSE
FALSE
FALSE
TRUE
(MVLowLmt:=0.0,
MVUpLmt:=100.0,
ManResetVal:=0.0,
MVTrackSw:=FALSE,
MVTrackVal:=0.0,
StopMV:=0.0,
ErrorMV:=0.0,
Alpha:=0.65,
ATCalcGain:=1.0,
ATHystrs:=0.2)
(SampTime:=T#250ms,
RngLowLmt:=-200.0,
RngUpLmt:=1300.0,
DirOpr:=FALSE)
0.0
FALSE
WORD#16#0
FALSE
0.0
FALSE
FALSE
[8((PB:=10, TI:=T#233s,
TD:=T#60s))]
FALSE
0.0
0.0
Constant
---
Channel measured value (REAL)
---
Output bit
Comment
Clock information
AC_StepProgram com-
pletion
PIDAT instruction execu-
tion condition
Manual/auto control
Autotuning execution
condition
Autotuning execution
condition for previous
task period
Operation setting param-
eters
Initial setting parameters
Manual manipulated vari-
able
Autotuning busy
PIDAT error code
PIDAT error
Manipulated variable
Autotuning normal com-
pletion
TimeProportionalOut
error
Storage array for opti-
mum PID parameters
Enable for TimePropor-
tionalOut
Minimum pulse width
Delay
Comment
2-793
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents