2 Instruction Descriptions
Structure Specifications
The data type of operation setting parameter OprSetParams is structure _sOPR_SET_PARAMS. The
specifications are as follows:
Name
OprSetParams
MVLowLmt
MVUpLmt
ManResetVal Manual Reset
MVTrackSw
MVTrackVal
StopMV
ErrorMV
Alpha
ATCalcGain
ATHystrs
* MVLowLmt must be less than MVUpLmt.
The data type of initial setting parameter InitSetParams is structure _sINIT_SET_PARAMS. The speci-
fications are as follows:
Name
InitSetParams
SampTime
RngLowLmt
RngUpLmt
DirOpr
* RngLowLmt must be less than RngUpLmt.
2-666
Meaning
Description
Operation
Parameters that are set
Setting
during operation.
Parameters
MV Lower
The lower limit of the
Limit
MV.
MV Upper
The upper limit of the
Limit
MV.
The value of MV when
Value
the deviation is 0 for the
proportional action.
MV Tracking
TRUE: ON
Switch
FALSE: OFF
MV Tracking
The value that is set in
Value
MV during MV tracking.
Stop MV
The value that is set in
MV when instruction
execution is stopped.
Error MV
The value that is set in
MV when an error
occurs.
2-PID
The set point filter is dis-
Parameter α
abled if the set point filter
coefficient α is 0.
Autotuning
Adjustment coefficient
Calculation
from autotuning results.
Gain
Stability is given higher
priority with higher val-
ues. The speed of
response is given higher
priority with lower val-
ues.
Autotuning
The hysteresis of the
Hysteresis
limit cycle.
Meaning
Description
Initial Setting
Initial setting parameters. _sIN-
Parameters
Sampling
The period for PID pro-
Period
cessing.
Lower Limit of
The lower limit of PV and
Input Range
SP.
Upper Limit of
The upper limit of PV and
Input Range
SP.
Action
TRUE: Forward action
Direction
FALSE: Reverse action
Data type
Valid range
_sO-
---
PR_SET_PAR
AMS
REAL
−320 to 320*
REAL
−320 to 320
REAL
BOOL
Depends on
data type.
REAL
REAL
−320 to 320
REAL
REAL
0.00 to 1.00
REAL
0.1 to 10.0
REAL
Data type
Valid range
---
IT_SET_PAR
AMS
TIME
T#0.0001s to
#100.0000s
REAL
−32000 to
32000*
REAL
BOOL
Depends on
data type.

NY-series Instructions Reference Manual (W560)

Unit
Default
---
---
0
100
%
0
---
FALSE
0
%
0.65
1.0
---
% FS
0.2
Unit
Default
---
---
s
T#0.1s
0
100
---
FALSE