Test Run In Monitor Mode - Omron SYSMAC CPM2B Operation Manual

Hide thumbs Also See for SYSMAC CPM2B:
Table of Contents

Advertisement

Programming Example
7-3-5

Test Run in MONITOR Mode

1,2,3...
160
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Switch the CPM2B in MONITOR mode and check the operation of the pro-
gram.
1. Set the Programming Console's mode switch to MONITOR mode.
MONITOR
RUN
PROGRAM
2. Press the CLR Key to bring up the initial display.
3. Force-set the start input bit (IR 00000) from the Programming Console to
start the program.
MONTR
The cursor in the lower left corner of the display indicates that the force set
is in progress. The bit will remain ON as long as the Set Key is held down.
4. The output indicator for output IR 01000 will flash ten times if the program
is operating correctly. The indicator should go OFF after ten one-second
flashes.
There is a mistake in the program if the output indicator doesn't flash. In
this case, check the program and force set/reset bits to check operation.
<MONITOR>
00000
CLR
00000
LD
LD
00000
^ OFF
00000
SET
~
ON
Section 7-3
BZ
00000

Advertisement