Electrical installation
8.15
Digital and analog inputs and outputs
8.15.1
Analog inputs (X3)
The servo amplifier is fitted with two programmable differential inputs for analog
setpoints. AGND (X3/7) must always be joined to the GND of the controls as a ground
reference.
Technical characteristics
—
—
—
—
—
Analog-In 1 input (terminals X3/3-4)
Differential input voltage max. ± 10 V, resolution 14-bit, scalable.
Standard setting : speed setpoint
Analog-In 2 input (terminals X3/5-6)
Differential input voltage max. ± 10 V, resolution 12-bit, scalable.
Standard setting : torque setpoint
Application examples for setpoint input Analog-In 2:
—
—
—
Defining the direction of rotation
Standard setting : clockwise rotation of the motor shaft (looking at the shaft end)
—
—
To reverse the direction of rotation, swap the connections to terminals X3/3-4 or X3/5-6
respectively, or change the ROTATION DIRECTION parameter in the "Speed controller"
screen page.
92
Differential-input voltage max. ± 10 V
Ground reference AGND, terminal X3/7
Input resistance 2.4 kW
Common-mode voltage range for both inputs ± 10 V
Update rate 62,5 µs
90k
10k
90k
10k
10n
10n
90k
10k
90k
10k
1n
1n
adjustable external current limit
reduced-sensitivity input for setting-up/jog operation
pre-control / override
Positive voltage between terminal X3/3 (+ ) and terminal X3/4 ( - ) or
Positive voltage between terminal X3/5 (+ ) and terminal X3/6 ( - )
02/2017
S300
X3
Analog-In 1+
3
4
Analog-In 1-
7
AGND
Analog-In 2+
5
6
Analog-In 2-
Kollmorgen
control
+
setpoint 1 +/-10V
ref. to CNC-GND
-
CNC-GND
+
setpoint 2 +/-10V
ref. to CNC-GND
-
GND
S300 Instructions Manual