Approvals; Conformance With Ul And Cul - Kollmorgen SERVOSTAR 300 Instruction Manual

Digital servo amplifier
Hide thumbs Also See for SERVOSTAR 300:
Table of Contents

Advertisement

Kollmorgen
4

Approvals

Certificates can be found in our Product Wiki on page Approvals.
4.1

Conformance with UL and cUL

This servo amplifier is listed under UL file number E217428.
UL (cUL)-certified servo amplifiers (Underwriters Laboratories Inc.) fulfil the relevant U.S.
and Canadian standard (in this case UL 840 and UL 508C). The UL certification relates
only to the mechanical and electrical construction design of the device.
This standards describe the fulfillment by design of minimum requirements for electrically
operated power conversion equipment, such as frequency converters and servo amplifi-
ers, which is intended to eliminate the risk of fire, electric shock, or injury to persons,
being caused by such equipment. The technical conformance with the standards is deter-
mined by an independent UL inspector through the type testing and regular checkups.
Apart from the notes on installation and safety in the documentation, the customer does
not have to observe any other points in direct connection with the UL (cUL)-certification of
the equipment.
UL 508C: UL 508C describes the fulfillment by design of minimum requirements for elec-
trically operated power conversion equipment, such as frequency converters and servo
amplifiers, which is intended to eliminate the risk of fire being caused by such equipment.
UL 840: UL 840 describes the fulfillment by design of air and insulation creepage spac-
ings for electrical equipment and printed circuit boards.
Markings
l
l
l
l
l
l
l
l
l
S300 Instructions Manual
Use 60°C or 75°C copper wire only.
Use Class 1 wire only.
Tightening torque for field wiring terminals
X0,X8,X9: 0.5 - 0.6Nm (4.43 to 5.31 lbf in)
Use in a pollution degree 2 environment.
These devices provide solid state motor
overload protection at 130% of full load
current.
Integral solid state short circuit protection
does not provide branch circuit protection.
Branch circuit protection must be provided
in accordance with the National Electrical
Code and any additional local codes.
These devices are not provided with motor
over-temperature sensing.
Suitable for use on a circuit capable of de-
livering not more than 42kA rms symmetri-
cal amperes for a max. voltage of 480 Vac.
The drives may be connected together via
the "common bus" (DC bus link) based on
the instructions on p. 61ff. The devices
may also be grouped from the AC input
side based on the max. input fuse (e.g.
3xS346 with one common 6A fuse in line).
02/2017
Marquages
l
Utilisez un fil en cuivre 60°C ou 75 °C min..
l
Utilisez seulement un fil de classe 1.
l
Couples de serrage recommandée
X0,X8,X9: 0.5 - 0.6Nm (4.43 ... 5.31 lbf in)
l
Utilisation dans un environnement de pollu-
tion de niveau 2.
l
Ces variateurs offrent une protection contre
les surcharges de moteur à semi-conduc-
teur à 130 % du courant FLA nominal.
l
Une protection de court-circuit à
semi-conducteur intégrale ne fournit pas de
protection de la dérivation. Il convient de
garantir une protection de la dérivation
conforme au NEC (National Electrical Code)
et aux réglementations locales en vigueur,
ou aux directives équivalentes applicables.
l
Ces variateurs n'offrent pas de capteurs de
température excessive.
l
Ce produit est conçu pour une utilisation sur
un circuit capable de fournir 42kA
symétriques (rms) maximum pour 480V.
l
Les variateurs peuvent être reliés entre eux
via le "bus commun CC" sur la base des in-
structions de la p. 61ff. Les variateurs
peuvent être groupés d'entrée AC basé sur
le max. fusible d'entrée (par exemple
3xS346 avec un fusible de 6A commune).
Approvals
17