8.14

Digital and analog inputs and outputs

8.14.1

Analog Inputs (X3B)

The servo amplifier is fitted with two programmable differential inputs for analog set-
points. AGND (X3B/13) must always be joined to the GND of the controls as a ground
reference.
Technical characteristics
Analog-In 1 input (terminals X3B/10-9)
Differential input voltage max. ± 10 V, resolution 16 Bit (accuracy 13 Bit), scalable.
Standard setting: speed setpoint
Analog-In 2 input (terminals X3B/12-11)
Differential input voltage max. ± 10 V, resolution 16 Bit (accuracy 13 Bit), scalable.
Standard setting: torque setpoint
Application examples for setpoint input Analog-In 2:
If an input was freshly assigned to a pre-programmed function, then the data set must be
saved in the EEPROM of the servo amplifier and a reset has to be carried out (with the
amplifier setup software for example).
Defining the direction of rotation
Standard setting : clockwise rotation of the motor shaft (looking at the shaft end)
To reverse the direction of rotation, swap the connections to terminals X3B/10-9 or
X3B/12-11 respectively, or change the COUNT DIRECTION parameter in the "Feedback"
screen page.
S701...S724 (single channel STO) Instruction Manual
Differential-input voltage max. ± 10 V
Ground reference AGND, terminal X3B/13
Input resistance 150 kW
Common-mode voltage range for both inputs ± 10 V
Update rate 62.5 µs
adjustable external current limit
reduced-sensitivity input for setting-up/jog operation
pre-control / override
Positive voltage between terminal X3B/10 (+ ) and terminal X3B/9 ( - ) or
Positive voltage between terminal X3B/12 (+ ) and terminal X3B/11 ( - )
12/2010a
S700
Electrical installation
81