22
Chapter 3 Installation and Wiring
3. Input/Output Terminals in Main Circuit
1) Applicable models:
EV2000-4T0055G/0075P~EV2000-4T0150G/0185P
R
S
T
P1 (+) PB (-) U
POWER SUPPLY
Table 3-3 Terminals of main circuit
Terminals
R, S, T
3-phase 380V AC supply input terminals
Reserved terminals for DC reactor,
P1, (+)
connected with copper bar before
delivery.
(+), PB
Reserved terminals for braking resistor
(-)
Output terminal for DC Minus Bus
U, V, W
3-phase AC output terminals
PE
Earth terminal
Notes:
Terminals PB of EV2000-4T0110G/0150P and
EV2000-4T0150G/0185P are suspended.
2) Applicable models:
EV2000-4T0185G/0220P~EV2000-4T0450G/0550P
R
S
T
P
P1
POW ER SUPPLY
Table 3-4 Terminals of main circuit
Terminals
3-phase 380V AC supply input
R. S. T
terminals
Positive pole of the rectifying bridge
P
Reserved terminals for DC reactor,
connected by copper bar before
P1, (+)
delivery
Output terminal for DC Minus Bus
(-)
3-phase AC output terminals
U. V. W
Earth terminal
PE
3) Applicable models:
EV2000-4T0550G. EV2000-4T0750P
Top:
(-) (+) P1
Bottom:
V
W PE
MOTOR
Function
U
V
W
(+) (-)
MOTOR
Function
R
S
T
POWER SUPPLY
U
V
W PE
MOTOR
EV2000 Series Universal Variable Speed Drive User Manual
Table 3-5 Terminals of main circuit
Terminal
R, S, T
P1, (+)
(-)
U, V, W
PE
4) Applicable models:
EV2000-4T0750G~EV2000-4T2200G
EV2000-4T0900P~EV2000-4T2800P
Top:
Bottom:
Table 3-6 Terminals of main circuit
Terminals
R. S. T
P1. (+)
PE
(-)
U. V. W
PE

3.3.2 Wiring of Control Circuit

1. Terminals and jumpers of control board
Locations of terminals CN5, CN6 and CN7 and jumpers
CN10, CN14, CN16 and CN17 are shown in Fig. 3-.
Terminal functions are given in Table 3-6. Refer to table
3-7 for the functions and settings of jumpers. Wire the
terminals and set the jumpers correctly before using the
Drive. It is recommended to use cables bigger than
2
1mm
to connect to the terminals.
Function
3-phase 380V AC supply input terminals
Reserved terminals for DC reactor
Output terminal for DC Minus Bus
3-phase AC output terminals
Earth terminal
R
POWER SUPPLY
U
V
W P1 (+) (-) PE
MOTOR
Function
3-phase 380V AC supply input
terminals
Reserved terminals for DC reactor
Output terminal for DC Minus Bus
3-phase AC output terminals
Earth terminal
S
T

Hide quick links: