Appendix E Error Codes / Messages; Operational Mode Error Codes - GSE 60 SERIES Technical Reference Manual

Programmable process controllers
Table of Contents

Advertisement

Appendix E
M
ESSAGE
Code02
CoDE03
CoDE04
CoDE05
CoDE06
CoDE07
CoDE08
Error Codes / Messages
This sections describes all error codes generated by 60 Series
instruments. Most error codes show a two-digit code reference along with
a short text message. Possible causes and remedies are described for
each error.
O
PERATIONAL
C
ODES
Input signal less than negative full scale. If this is due to excessive loading, reduce the
load. Otherwise check the load cell connections. If a 4 wire load cell cable is being used,
Under
check that the sense jumpers are in place. Verify that the capacity selection P110 is
Load!
correct. Use the information parameters, especially P61103 and P61104, to check the
setup and input signal.
Over-
Input signal is greater than positive full scale. Use same check as for underload.
Load!
Number to be displayed will not fit within 6 digits. This will not normally occur for the
#>
Gross, Net or Tare Weights but may result while displaying the accumulated totals if the
Dsply
amount exceeds 999,999. Either clear the totals or settle for only being able to transmit
the totals.
An attempt was made to zero out more than allowed per P118 selection. Use the
Zero>
[TARE] key for subtracting off container weights or if large dead-load is always to be
Max.!
present, apply this dead-load during the No Load? prompt during calibration to
permanently eliminate the offset.
Tare>
Tare entry was greater than full scale. Most likely the entered tare value was incorrect.
F.S.!
Tare<
Negative tare attempted, but not allowed per P162. For auto-tares, the GROSS Weight
0!
must be greater than zero unless P162 is changed to allow negative tares.
The signal into the A/D is greater than +/- 2 times the expected full scale signal. For
Check
example if the full scale capacity at P110 is 100, then the error message will be
Conn
displayed at +/- 208 taking into consideration the 4% overload. This error usually
indicates a defective or incorrectly wired load cell.
M
E
ODE
RROR
D
ESCRIPTION
E-1

Hide quick links: