9-100 Chapter 9
Example:
Changing the Filter Setting While Filling
This setup changes the filter setting during a filling
process. The filter is set to a low value during the
fast fill process to provide a fast response to the
rapidly changing weight. When the fast fill target
is reached, macro 12 is invoked to begin the slow
fill. The filter setting is increased to provide a
more stable weight reading as it approaches the
final target. Once the target is achieved, the default
filter setting is restored to 2.0 seconds providing a
stable static weight display.
===================================
116%s5%e
fltr1 2.0 s
MACRO #6 – START FAST FILL
2%k
set 0.25 second filter
activate fast output
1%A
MACRO #12 – START SLOW FILL
set 0.5 second filter
3%k
activate slow output
2%A
MACRO #13 – FILL COMPLETE
set default filter (2 sec)
*%k
Fill Done!%S%P
prompt
GSE Scale Systems
128%j
Checks if [F1] key is held.
133%j
Checks if [START] key is held on 660 Series.
Checks if remote key #1 is held on 460 / 560 Series.
%j
Checks if any key is held.
D
F
%k
IGITAL
ILTER
Syntax
Get Current Filter
%k
Set Filter
< filter# > %k
Restore Default Filter
*%k
Clear Rate Filter History
R%k
Arguments
filter#
Select one of the following filter numbers:
0.06 seconds
0.13 seconds
0.25 seconds
0.50 seconds
1.00 seconds
2.00 seconds
4.00 seconds
8.00 seconds
No filtering
Notes
The filter# argument does not change the setup mode
selection at P116, rather it temporarily changes the filter
until power is interrupted or upon saving changes when
exiting the setup mode.
Auto-filter selections cannot be selected with the %k
command, but can be restored with the *%k command.
Get Current Filter
%k