Diagnostic Parameters - GSE 60 SERIES Technical Reference Manual

Programmable process controllers
Table of Contents

Advertisement

Table 14-6: Diagnostic Parameters
D
P
IAGNOSTIC
ARAMETER
P6200)
Dsply
Test
P6200!
OpRAM
Test
P6200@
EEROM
Test
P6201)
AnOut
P6201!
0-10—
0.00v
P6201@
0-20—
0.00A
P6201#
4-20—
4.00A
P6400)
Send
Setup
P6400!
Send
All
P6410)
LnCnt
P6410!
ErCnt
P6410@
1stEr
None!
P6410#
Debug
Off
D
IAGNOSTIC
The parameters listed in Table 14-6 provide valuable information regarding
the integrity of system memory and parameter setup file transfers.
Performs display test. Press [ENTER] to illuminate all segments and pixels of the
7-segment VF display. Press any key to exit display test mode.
Tests the integrity of the optional RAM (database). Press [ENTER] to initiate test.
On the 460 Series, this procedure tests the 4K EEPROM database memory.
Tests the integrity of the E
initiate test.
Used to enter the analog output number for P62011 à P62013. For example, key
1
in 2 [ENTER], then access P62011 à P62013 to perform tests for analog output #2.
Used to test the linearity of the 0-10VDC analog output. Press [ENTER] to toggle
the analog output through 0V, 2V, 4V, 6V, 8V and 10V, or key in a value within the
output range and press [ENTER].
Used to test the linearity of the 0-20mA analog output. Press [ENTER] to toggle the
analog output through 0mA, 5mA, 10mA, 15mA, and 20mA, or key in a value within
the output range and press [ENTER].
Used to test the linearity of the 4-20mA analog output. Press [ENTER] to toggle the
analog output through 4mA, 8mA, 12mA, 16mA, and 20mA, or key in a value within
the output range and press [ENTER].
Transmits all setup parameters out a specified communication port. Data is
transmitted in ASCII text format.
Same as P64000 with the addition of operating parameter values such as variables,
totals, tare weight, etc.
Displays the number of lines received while uploading a setup file. The line count is
0
reset to zero (0) whenever the setup access code is received.
Displays the number of errors encountered while uploading a setup file.
0
Displays the parameter number and line number of the first error encountered while
uploading a setup file.
Enables/disables the transmission of each error encountered while uploading a
setup file.
P
ARAMETERS
D
ESCRIPTION
2
(U27 & U28 on the main board). Press [ENTER] to
60 Series Technical Reference Manual
Information Parameters 14-11

Hide quick links: