8-50 Chapter 8
GSE Scale Systems
230%s3%e
P230.01 (instance 3)
231%s2%e
P231.02 RxTyp Line
232%s%c%e
P232.03 RxFmt
P%e
%e80.2%e%e
P/N:
.013%e
<CR> ^M=13
233%s3%e
P233.02 RxMac 3
221%s10%e
P221.10 RxTrm <LF>
230%s4%e
P230.01 (instance 4)
231%s2%e
P231.02 RxTyp Line
232%s%c%e
P232.03 RxFmt
S%e
%e80.3%e%e
S/N:
.013%e
<CR> ^M=13
233%s4%e
P233.04 RxMac 4
%z
Exit Setup Mode
Several transmissions were tested with a 660 that has the above
setup. These are shown below along with their respective results.
T
B
-
RANSMITTED OR
AR
D
CODED
ATA
Q123
Q 234
Q 345hello
Q321 987
P10-40-5503
P 09-30-0238
P200550-00000
MPNOT STORED
MP NOT STORED
S112233
S112-233
R
ESULT
Stores "123" into STR 4.
Stores "234" into STR 4 (leading space ignored).
Stores "345" into STR 4 (hello is stripped off
since STR 4 is a numeric field).
Stores "321" in STR 4 (" 987" is lost due to
space).
Stores "10-40-5503" into STR 2.
Stores "09-30-0238" in STR 2 (does not store
leading space!).
Stores "200550-000" in STR 2 (loses last two
"0"s since STR size is only 10!
Nothing stored! "M" not defined, "P" not first.
Nothing stored! "M" not defined, "P" not first.
Stores "112233" into STR 3.
Stores "112-233" into STR 3.