NSTALLATION
The procedure for installing a 660, 661 and 662 panel mount controller is
identical.
Figure 2-10: 660, 661 and 662 Panel Mount Cut-Out
To install panel-mount 660, 661 and 662 controllers:
1. Make a cut out in the panel using the dimensions shown in Figure
2-10.
The corners are typically 0.1R maximum.
2. Remove the 8 hex nuts holding the main board front panel to the back
bracket.
3. Make sure the gasket remains on the front panel side. When installed,
the gasket will be compressed against the front of the enclosure
cutout.
4. Position the main board front panel inside the cutout making sure the
keypad is facing in the correct upright position.
5. From the inside of the enclosure fit the back bracket over the studs on
the main board front panel.
6. Install the 8 hex nuts from the inside of the panel.
7. Tighten nuts until they are hand tight and pressing against the back
panel surface. Then tighten each nut by 3/4 turn to compress the
gasket to the front of the panel.
Installation 2-15