Section 3 - Operation; Circuit Breaker Opening; Waveform Capture; Event Logging - GE EntelliGuard TU Installation, Operation And Maintenance Manual

Trip unit
Table of Contents

Advertisement

09/25/08
SECTION 3 – OPERATION
WARNING
IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Ensure only qualified personnel install, operate,
service and maintain all electrical equipment.
Failure to comply with these instructions could
result in death or serious injury.
WARNING
PERSONAL INJURY
Avoid risk of injury from moving parts while
handling the circuit breaker.
If advisable, use a cable/busbar lockable
grounding device (optional accessory) to provide
additional safety during system maintenance.
Failure to comply with these instructions could
result in death or serious injury.
CAUTION
PRODUCT DAMAGE
Ensure circuit breaker and its accessories are
always used within their designated ratings.
Use the specially designed circuit breaker
handling truck (optional accessory) when
removing the circuit breaker from its cassette.
Failure to comply with these instructions may
result in product damage.
NOTICE
Each charging action provides sufficient charge
for an Open-Close-Open Operation without
requiring additional charging.
The mechanism works properly only when the
circuit breaker is mounted on a horizontal plane
with bottom mounting or on vertical plane with
front mounting.

CIRCUIT BREAKER OPENING

NOTICE
Tripping under fault conditions will be automatic
depending on the protective device installed and its
settings.

WAVEFORM CAPTURE

A total of eight cycles are captured:
Four pre-trigger.
Four post-trigger.
© 2008 General Electric All Rights Reserved
Courtesy of NationalSwitchgear.com
24 V external power is required for this feature.
When waveform capture is executed, the following
channels will be captured simultaneously: Phase A
current, Phase B Current, Phase C Current, Phase L1
voltage, Phase L2 voltage, Phase L3 voltage. See Table 17.

Table 17: Trigger Waveform Capture Events

Event
Manual trigger over
communications
Over current (GF, ST, LT, Inst)
Protective relays
Current alarm 1
Current alarm 2

EVENT LOGGING

The trip unit keeps a log of the last 10 events:
Over current trips
Protective relay trips
Shunt trip (PBII and Global EntelliGuard G Trip Units
Only)
Under voltage Release trip (PBII and Global
EntelliGuard G Trip Units Only)
BIM Trip Unit Mismatch - Breaker Interface Module
The following information is stored with each event:
RMS currents
Phase
Type of trip
Trip counter
Time and date stamps
Trips are logged under self power without time stamp.
Events with time stamps are only logged when 24 V
control power is available.
All setup, status and metering information is accessed
through five keys whose functions are:
Up: Scroll up or increment value
Down: Scroll down or decrement value
Right: Next function or next page
Left: Previous function or previous page
Enter: Save or setting in to memory
EntelliGuard®TU Trip Unit
Section 3 – Operation
Waveform Capture
Setpoint
ON, OFF
ON, OFF
ON, OFF
ON, OFF
ON, OFF
19