Use Of Usb Sticks; X3 Serial Communication Rs-232 / Can1; X4 Digital Input And Power Supply - Parker PAC120 Operation Manual

Automation controller
Hide thumbs Also See for PAC120:
Table of Contents

Advertisement

Parker Automation Controller
PAC120
4.5.3 USB Sticks
USB stick users should consider the following points:
• The USB port is mechanically designed to support up to 1,000 plug/unplug operations.
• Pulling off a USB stick during operation is allowed only when no more file operations are being performed. Fail-
ure to comply may render the USB stick useless!
• If a program still has a file open when the USB stick is pulled, you will find it impossible to close the directory that
the file belongs to. In this situation, the system will not respond to any file or directory operation requests because
it would be expected to read from a device that is no longer available. Therefore, before pulling off the USB stick,
you should always ensure that no program still has an open file loaded from the stick.
• Before pulling off the stick, always use the function USB_UMountDisk from the Parker System Library iMX6
• USB sticks can be found under the following path: \media\usbx (x = 1..n number of plugged USB sticks)
• Supported format(s): FAT32

4.5.4 X3 Serial Communication RS-232 / CAN1

The CAN interface complies with standard ISO 11898 and supports baud rates of up to 1 Mbps. It is electrically in-
sulated.
Pin wiring RS 232 interface:
X8 RS 232 interface
Connector
Weidmüller B2L
3,5/10/180LH
SN BK BX SO
1338740000
NOTE
You may connect the CAN bus termination directly to the pins.

4.5.5 X4 Digital Input and Power Supply

On-board power supply unit
The PAC Controller features an on-board power supply unit (PSU) designed for an input voltage of 24 VDC (18 V ...
32 V). The PSU is protected against reverse polarity. It supplies power to the PAC120's CPU core and to the PACHC
and PACIO modules connected to the E-bus. The modules themselves require their own power supply.
Verify that both the cord and the PSA are externally protected against short circuit and overload triggering at max. 10 A.
Pin wiring:
X9 24 VDC power supply
Connector
Weidmüller
Pin
Function
1
RXD
2
TXD
3
GND
4
Shield
5
Shield
Pin
Function
1
Digital input
External power supply
2
24 VDC (18 V ... 32 V)
3
External power supply, GND
Pin wiring CAN interface:
X8 CAN interface
Connector
Weidmüller B2L
3,5/10/180LH
SN BK BX SO
1338740000
Product Description
Pin
Function
6
CAN_H
7
CAN_L
8
CAN_GND
9
CAN_H
10
CAN_L
21

Advertisement

Table of Contents
loading

Table of Contents