Section 6
LHMI engineering
6.1.1.1
86
HMI display page
Symbol library
GUID-8843160D-28CC-46D5-8045-445FAAB335B9-ANSI V1 EN
Figure 58:
Graphical Display Editor: an active view
The Graphical Display Editor has a fixed symbol library window on the left side of the
view. The presentation is empty when no page exists for the IED. A default single-line
diagram presentation is displayed if standard configurations are used.

Display window and sequence order

There are rules for handling the HMI pages.
IED supports one bay with one single-line diagram.
Measurements and the single-line diagram can be displayed on the page in any
possible order and placement.
All symbol objects, for example apparatus and measurement, on the HMI page
must be linked to the correct function block in the application configuration in
order to present the correct process values.
IED HMI display
window
window
1MAC108982-MB A
615 series ANSI
Engineering Manual