Download  Print this page

Mitsubishi Electric GOT 1000 Series Manual Page 57

Graphic operation terminal.
Hide thumbs

Advertisement

(b) When busy (Interval that trigger conditions are met is shorter than processing time of action)
• Tag data and time that conditions are met are stored to the trigger buffer every time the conditions are
met.
• If an action cannot complete before another condition is met, up to 128 trigger data can be stored.
[GOT]
[When busy]
Job 1 ... 1)
Trigger conditions
Job 1 ... 2) Trigger data (Tag data and time)
are met
Job 3 ... 3) Trigger data (Tag data and time)
Job 1 ... 2)
Trigger conditions
are met
Job 3 ... 3)
Trigger conditions
are met
Time
The numbers 1) to 3) correspond to the order of that trigger conditions are met.
In this example, the jobs 1 and 3 access the same database.
(c) When becoming less busy (Interval that trigger conditions are met is longer than processing time of action)
• The action, which is specified by the data stored in the trigger buffer, is read and executed sequentially.
• When the action for the trigger data in the trigger buffer completes, the trigger data is cleared, and
another trigger data can be stored.
[GOT]
[When becoming less busy]
Time
The numbers 1) to 3) correspond to the order of that trigger conditions are met.
In this example, the jobs 1 and 3 access the same database.
POINT
POINT
POINT
(1) For job operation for which [Trigger buffering] is disabled, refer to the following:
5.3 (1) Operation behavior of jobs
(2) Whether the condition is changed from false to true is judged at collection of the tag.
6.7.2 Setting items in Trigger conditions
Trigger buffer
Job 1 ... 1)
Action is
executed
Trigger buffer
Job 1 ... 2)
Action is
executed
Job 3 ... 3)
Action is
executed
Data
trans-
mission
Database
The action for "Job 1 ... 1)" is executed.
The trigger data of "Job 1 ... 2)" and
"Job 3 ... 3)" is stored to the trigger buffer.
Time
Data
trans-
mission
Database
The action for "Job 1 ... 1)" is executed.
The action for "Job 1 ... 2)" and "Job 3 ... 3)",
which is specified by the data in the trigger
buffer, is executed sequentially.
Time
5.1 DB Interface Function
1
2
3
4
5
6
7
8
5 - 7