Suzuki 2006 SX4 Service Manual page 961

Hide thumbs Also See for 2006 SX4:
Table of Contents

Advertisement

7) When refrigerant container (1) is emptied, use the
following procedure to replace it with a new
refrigerant container.
a) Close low pressure valve.
b) Replace empty container with a refrigerant
container which has been charged with
refrigerant. When using refrigerant container tap
valve (2), use the following procedure for
replacement.
i)
Retract needle (3) and remove refrigerant
container tap valve by loosening its plate nut
(4).
ii) Install the refrigerant container tap valve to a
new refrigerant container.
c) Purge any air existing in center charging hose.
When using refrigerant container tap valve, use
the following procedure to purge air.
i)
Once fully tighten refrigerant container tap
valve (1), and then loosen (open) plate nut
(2) slightly.
ii) Open low pressure side valve (3) of manifold
gauge set (4) a little.
iii) As soon as refrigerant comes out with a
"hiss" through a clearance between
refrigerant container and tap valve, tighten
plate nut as well as low pressure side valve.
iv) Turn handle of tap valve clockwise so that its
needle is screwed into the new container to
make a hole for refrigerant flow.
Air Conditioning System: Manual Type 7B-21
8) After the system has been charged with specified
amount of refrigerant or when low pressure gauge
(1) and high pressure gauge (2) have indicated the
following specified value, close low pressure side
valve (3) on manifold gauge set (4).
Specified amount of refrigerant
430 ± 20 g (15.2 ± 0.7 oz))
Low side and high side pressure example
Gauges should read as follows when ambient
temperature is 30 °C (86 °F).
Pressure
on high pressure gauge
Pressure
on low pressure gauge
I2RH01720018-01
Removal of Manifold Gauge Set
WARNING
!
High pressure side is under high pressure.
Therefore, be careful not to get injured
especially on your eyes and skin.
For the A/C system charged with the specified amount of
refrigerant, remove manifold gauge set as follows:
1) Close low pressure side valve of manifold gauge set.
(The high pressure side valve is closed continuously
during the process of charging.)
2) Close refrigerant container valve.
3) Stop engine.
4) Using shop rag, remove charging hoses from service
valves. This operation must be performed quickly.
5) Put caps on service valves.
I2RH01720019-01
1130 – 1560 kPa
(11.4 – 15.6 kgf/cm
(162.3 – 221.8 psi)
270 – 390 kPa
(2.7 – 3.9 kgf/cm
(38.8 – 56.0 psi)
4
2
1
3
2
)
2
)
I7RW01721013-02

Advertisement

Table of Contents
loading

Table of Contents