[P11] Functions Menu - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

2.5.3

[P11] Functions Menu

Accessible from: "Factory" group.
Mask of the terminal
Functions
Functions
--------------- P11.01
Air flow control type:
Disabled
Functions
--------------- P11.36
Fans type:
EC 0-10V
--------------- P11.02
Amount of EC fans:
Functions
--------------- P11.11
Fan special function
01 enable:
Functions – Q.Restart
--------------- P11.37
Quick Restart function
enable:
Functions – Q.Restart
--------------- P11.38
K value of the EC
fan:
0046
Version 38
Access mask to "Functions" menu.
Air flow control type.
Disabled | Constant Range | Constant DeltaP | Read Only DeltaP | Read Only Rate].
Always disabled on PMESH units.
Parameter for setting the fan type.
[AC | EC 0-10V | EC ModBus EBM].
Parameter for setting the number of fans.
Visible only on units with EC fans.
1
Enable special function 01 of the fans.
N
Parameter for enabling the Quick Restart function.
N
Constant K value of EC fans.
Description
Par.N.
11.01
11.36
11.02
11.11
11.37
11.38
48

Advertisement

Table of Contents
loading

Table of Contents