Limiting Parameters - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

2.6.6

Limiting parameters

Par.N.
Minimum limit that can be set for the internal fan speed
(Calculated as P10.10 – P10.11%)
99.01
Minimum limit that can be set for the dehumidification setpoint
99.02
(Calculated as P50.04 + 5)
Maximum limit that can be set for the dehumidification setpoint
99.03
(Calculated as P50.03 - 5)
99.04
Minimum limit that can be set for parameter P10.01 (type of unit)
99.05
Maximum limit that can be set for parameter P10.33 (type of unit)
99.18
Advanced time band enable limit, depends on the advanced time band enable
P900.01
(Equal to 1 with standard programming, 4 with advanced programming)
99.19
Minimum value that can be set for time band control
(Equal to 1 – unit off)
99.20
Maximum value that can be set for time band control
(Equal to 2 – unit in adjustment)
99.21
Minimum limit of summer temperature setpoint for the control of time bands
depending on the active adjustment
(Equal to P20.24 with adjustment in return, P20.56 with adjustment in delivery)
99.22
Maximum limit of summer temperature setpoint for the control of time bands
depending on the active adjustment
(Equal to P20.25 with adjustment in return, P20.57 with adjustment in delivery)
99.23
Minimum limit of winter temperature setpoint for the control of time bands
(Equal to P20.26)
99.24
Maximum limit of winter temperature setpoint for the control of time bands
(Equal to P50.01)
Maximum value that can be set for low pressure setpoint for frost-free function
99.25
(Equal to 15 bar)
Minimum value that can be set for cooling setpoint depending on the active
adjustment
99.27
(Equal to P20.24 with adjustment in return, P20.56 with adjustment in delivery)
Maximum value that can be set for cooling setpoint depending on the active
adjustment
99.28
(Equal to P20.25 with adjustment in return, P20.57 with adjustment in delivery)
Maximum value that can be set for the type of signal used for setpoint compensation
(equal to 7 if at least one probe is enabled for calculating the return temperature,
99.29
otherwise 6)
Maximum value that can be set for the cold setpoint depending on the active
99.30
regulation (equal to the active cold setpoint).
99.31
Maximum value of units in LAN that can be set.
Version 38
Description
117