Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 77

Table of Contents

Advertisement

Mask of the terminal
Optional
--------------- P27.29
Diff. between setpoint
humidification and
dehumidification:
05%
Optional
--------------- P27.11
Damper enable:
--------------- P27.12
Damper opening time:
120sec
Optional
--------------- P27.13
Energy Analyzer 1
enable:
Optional – Enrg. Anlz.
--------------- P27.14
System type:
3-phase unbal ¾-wire
--------------- P27.15
Transformer ratio:
00020
Optional
--------------- P27.30
Energy Analyzer 2
enable:
Optional- Enrg. Anlz.2
--------------- P27.31
System type:
3-phase unbal ¾-wire
--------------- P27.32
Transformer ratio:
00020
Optional
--------------- P27.20
Setpoint Compensation
enable:
--------------- P27.21
Type of signal for
compensation:
0-1V
Optional
--------------- P27.22
Temp. for Min compens.
of cooling set: 24.0°C
--------------- P27.23
Temp. for Max compens.
of cooling set: 28.0°C
Version 38
Parameter for setting the minimum difference between humidification setpoint and
dehumidification setpoint.
Visible only if both the humidifier and the dehumidification function are enabled.
Enable the delivery air damper.
N
Opening stroke time for the damper.
Enable the network analyser.
N
Type of power supply system.
It can be a 1-2-3 phase power supply system with balanced or unbalanced load and
with or without neutral.
Input current transformation ratio.
Visible only if the network analyser is enabled.
Parameter for enabling the management of the network transducer 2 (N:disabled -
Y:enabled).
N
Parameter for configuring the power supply system that can be 1-2-3 phases with
balanced/unbalanced load, with or without neutral (Default: system 3/4 unbalanced
wires) and Parameter for configuring the supply current transformer ratio. (Default:
20):
Setpoint offset function enable.
N
Setpoint offset signal type.
[0-1V
| 0-5 V
| 0.5-4.5V
DC
DC
available)].
Parameter for setting the start point of cooling setpoint compensation.
Parameter for setting the end point of cooling setpoint compensation.
Visible only if the type of signal for the compensation of the setpoint is set to REM
T/H.
Description
| 0-20mA | 4-20mA | T+H Remote | External T+H (not
DC
Par.N.
27.29
27.11
27.12
27.13
27.14
27.15
27.30
27.31
27.32
27.20
27.21
27.22
27.23
77