Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 54

Table of Contents

Advertisement

Mask of the terminal
Regulations
--------------- P20.03
Fan modulation delay:
120s
Regulations
--------------- P20.04
Fan regulation delay:
060s
Regulations
--------------- P20.05
Regulation integral
time:
900s
Regulations
--------------- P20.08
Dirty filters sensor
presence:
--------------- P20.09
Fire/smoke sensor
presence:
Regulations
--------------- P20.10
Flooding sensor
presence:
Regulations
--------------- P20.13
Remote ON/OFF
presence:
Regulations
--------------- P20.18
Regulation band in
cooling:
01.5°C
--------------- P20.19
Regulation band in
heating:
01.5°C
Regulations
--------------- P20.20
Regulation band for
dehumidification:05%RH
--------------- P20.21
Regulation band for
humidification:
05%RH
Regulations
--------------- P20.22
Umidifier regulation
integral time:
900s
--------------- P20.23
Umidifier regulation
derivative time:
000s
Version 38
Ventilation modulation start delay.
Start regulation delay.
Integral adjustment time.
Only visible on units without inverter compressor.
Presence of the dirty filter sensor.
N
Presence of the Fire/Smoke detector.
N
Presence of the flooding sensor.
N
Parameter for configuring the ON/OFF remote contact (N:disabled - Y:enabled).
N
Cooling adjustment band.
Heating adjustment band.
Visible only when the heating resources are present.
Dehumidification adjustment band.
Humidification adjustment band.
Integral time for humidification adjustment.
Derivative time for humidification adjustment.
Visible only if humidifier management is enabled.
Description
Par.N.
20.03
20.04
20.05
20.08
20.09
20.10
20.13
20.18
20.19
20.20
20.21
20.22
20.23
54