Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 101

Table of Contents

Advertisement

Par.N.
22.76
Delay for decrease for air delivery control
22.77
Delay between two decreases for air delivery control
Port used for the Fieldbus (1:Fbus1 – 2:Fbus2)
22.78
22.79
Air flow alarm detection delay from ventilation start
22.92
Air flow alarm activation delay without compressors or heaters active
22.80
Dirty filters alarm delay
Flooding alarm type and reset configuration (0:Undefined – 1:Automatic
22.83
Signal – 2:Manual Signal – 3:Automatic Alarm – 4:Manual Alarm)
Phase sequence alarm reset configuration (3:Automatic Alarm – 4:Manual
22.84
Alarm)
Fire/smoke alarm type and reset configuration (0:Undefined – 1:Automatic
22.85
Signal – 2:Manual Signal – 3:Automatic Alarm – 4:Manual Alarm)
Enable external damper alarm control (0:Disabled – 1:Enabled)
22.88
22.94
Low delivery temperature alarm setpoint
22.95
High delivery temperature alarm setpoint
22.96
Low delivery humidity alarm setpoint
22.97
High delivery humidity alarm setpoint
23.01
Nominal speed of internal fan
23.01
Nominal speed of internal fan
Internal fan Economy Mode function configuration (0:Disabled – 1:Enabled)
23.02
23.03
Internal fan speed with Economy Mode enabled
Enable of no flow from flow switch on ID2 alarm (0:Disabled – 1:Enabled)
23.73
23.74
Enable of semi-automatic reset following no flow from flow switch alarm (0:
No – 1:Yes)
23.75
Count of flow switch alarm events
Enable of semi-automatic reset following no flow from fan alarm (0: No –
23.76
1:Yes)
23.77
Count of no flow from fan alarm events
I/O expansion 0-10Vdc fan alarm control enable (0:disabled – 1:enabled)
23.71
23.05
Minimum internal fan speed with modulation function active
23.07
Internal fan modulation function configuration for inverter compressor units
(0:Disabled – 1:Enabled)
23.08
Minimum modulation speed of the internal fan for inverter compressor units
(maximum reduction of design speed)
23.09
Internal fan low speed function configuration for inverter compressor units in
dehumidification (0:Disabled – 1:Enabled)
23.10
Fixed speed of the internal fan in inverter compressor units with
dehumidification Enabled
23.11
Air differential check time
EC condensation control function configuration (0:Disabled – 1:Enabled)
23.12
Heater post-ventilation configuration for unit OFF (0:Disabled – 1:Enabled)
23.61
23.62
Heater post-ventilation time
23.65
Set Constant Flow adjustment (Divided by 100)
Version 38
Description
Default
U.M.
Min.
300
s
0
600
s
0
2
-
1
45
s
15
5
s
0
8
s
2
4
-
0
3
-
3
4
-
0
0
-
0
10
°C
0
32
°C
20
30
%RH
0
80
%RH
30
70
%
P
99.01
70
%
P
99.01
0
-
0
50
%
0
0
-
0
0
-
0
0
-
0
0
-
0
0
-
0
0
-
0
40
%
0
1
-
0
50
%
0
1
-
0
60
%
P
99.01
60
s
0
0
-
0
1
-
0
60
s
1
25
m³/h
10
Max.
600
1200
2
180
180
180
4
4
4
1
30
50
70
99
100
100
1
99
1
1
5
1
5
1
P
23.01
1
P
10.11
1
P
10.10
999
1
1
999
400
101