Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 99

Table of Contents

Advertisement

Par.N.
20.72
T&H limits alarm delay when unit ON
Safety Reduction Load LP function configuration (0:Disabled – 1:Enabled)
20.73
20.74
Circuit 1 Safety Reduction Load LP function activation setpoint
20.75
Circuit 1 Safety Reduction Load LP function differential
20.76
Step time for Circuit 1 Safety Reduction Load LP function
Auxiliary humidity probe address 129 configuration (0:Disabled – 1:Enabled)
20.82
20.83
Configuration of the ventilation control function (special function
02)(0:Disabled – 1:Return T. – 2:Delivery T. – 3:Temperature Delta)
20.84
Differential for control of special fan function 02
Enable management of external fire control unit (0:Disabled – 1:Enabled)
20.94
21.21
Value of the cold ramp for maximum Free Cooling opening
Free Cooling damper adjustment configuration (0:Disabled – 1:Enabled)
21.09
Free Cooling damper control type configuration (0:Digital – 1:Modulating)
21.10
21.11
Setpoint (T_ROOM-T_EXTERNAL) for Free Cooling damper adjustment
21.12
Free Cooling damper adjustment band
21.13
Minimum Free Cooling damper opening
21.14
Maximum Free Cooling damper opening
21.32
Configuration of simultaneous operation of Direct Free Cooling and
compressor or 3-way valve
21.33
Direct Free Cooling activation delay after compressor shutdown/closing of
the water valves
21.15
Free Cooling management configuration for high humidity
21.16
Humidity limit for Free Cooling damper disable
21.17
Humidity band to disable Free Cooling damper
21.18
Free Cooling damper adjustment configuration with compressor alarm
(0:Disabled – 1:Enabled)
21.19
Setpoint (T_ROOM-T_EXTERNAL) to regulate the Free Cooling damper
with compressor alarm
21.20
Free Cooling damper adjustment band with compressor alarm
21.26
Enable washing mode (0:Disabled - 1:Enabled)
22.01
Low temperature alarm setpoint
22.02
High temperature alarm setpoint
22.03
Low humidity alarm setpoint
22.04
High humidity alarm setpoint
22.17
Step 1 heater operating hours for maintenance setpoint (Thousands)
22.18
Step 2 heater operating hours for maintenance setpoint (Thousands)
22.19
Humidifier operating hours for maintenance setpoint (Thousands)
22.20
Modulating heating element operating hours for maintenance setpoint
(Thousands)
Alarm reset by supervision system (0:Disabled – 1:Enabled)
22.21
Configuration of presence of KIPlink module (0:Disabled – 1:Enabled)
22.29
Version 38
Description
Default
U.M.
Min.
600
s
1
0
-
0
7.5
bar
5
1
bar
0
5
min
1
0
-
0
0
-
0
3
°C
0.1
0
-
0
50
%
0
0
-
0
0
-
0
3
°C
0
1
°C
0
0
%
0
100
%
P
21.13
0
-
0
180
s
0
0
-
0
60
%RH
0
1
%RH
0
0
-
0
1
°C
1
0.5
°C
0
0
-
0
10
°C
0
32
°C
20
30
%RH
0
80
%RH
30
0
h
0
0
h
0
0
h
0
0
h
0
0
-
0
0
-
0
Max.
999
1
9
1
99
4
3
9.9
1
100
1
1
50
9.9
100
100
1
9999
1
99.9
9.9
1
50
9.9
1
30
50
70
99
99
99
4
99
1
1
99