Mask of the terminal
Unit - Int. Fan Status
Fan 1 00 00000
Turned On
RPM:0800
No alarm
Fan 2 00 00000
Turned On
RPM:0800
No alarm
Unit - Int. Fan Status
Fan 3 00 00000
Turned On
RPM:0800
No alarm
Fan 4 08 01000
In alarm
RPM:0000
Motor overheating
Unit - Int. Fan Status
Fan 5 00 00000
Turned On
RPM:0800
No alarm
Fan 6 00 00000
Turned On
RPM:0800
No alarm
Unit - Condens. Valve
Circuit 1
Opening:
035%
Circuit 2
Opening:
000%
Unit - Energy Anlz. 1
Voltage (V)
231
Current (A)
035.1
Active Power(kW)0007.3
Unit - Energy Anlz. 1
Voltage (V)
L1-L2
403
L2-L3
403
L3-L1
403
Neutral 1
233
Neutral 2
233
Neutral 3
233
Unit - Energy Anlz. 1
Current (A)
Line 1
016.7
Line 2
016.7
Line 3
016.7
Neutral
000.0
Unit - Energy Anlz. 1
Active Power (kW)
Phase 1
0003.5
Phase 2
0003.5
Phase 3
0003.5
Total
0010.5
Version 38
Display of the status of the internal EC 1 and 2 fans communicating via Modbus.
In case of alarm or signal coming from the fan, both the code (alarm on the left,
signal on the right) and the corresponding description are visible.
Visible only on units with at least one ec fan controlled via serial communication.
Display of the status of the internal EC 3 and 4 fans communicating via Modbus.
In case of alarm or signal coming from the fan, both the code (alarm on the left,
signal on the right) and the corresponding description are visible.
Visible only on units with at least 3 ec fans controlled via serial communication.
Display of the status of the internal EC 5 and 6 fans communicating via Modbus.
In case of alarm or signal coming from the fan, both the code (alarm on the left,
signal on the right) and the corresponding description are visible.
Visible only on units with at least 5 ec fans controlled via serial communication.
Display of the opening of the condensation valve.
If the second circuit is available, opening of the condensation valve of circuit 2 is also
displayed.
If EC condensing fans are present, their speed is displayed instead of the opening of
the valves, and the valve icons are replaced with the fan icons (
Mask that displays the values detected by the network analyser.
The supply voltage, absorbed current and absorbed active power are displayed.
Visible if the network analyser is present and configured and the unit power supply is
single-phase.
Mask that displays the electric values detected by the network analyser.
It displays phase-phase and phase voltage (phase-neutral) values.
Visible if the network analyser is present and configured and the unit power supply is
three-phase.
Mask that displays the electric values detected by the network analyser.
Phase currents and neutral current are displayed.
Visible if the network analyser is present and configured and the unit power supply is
three-phase.
Mask that displays the electric values detected by the network analyser.
The phase active power and the total active power absorbed are displayed.
Visible if the network analyser is present and configured and the unit power supply is
three-phase.
Description
)
28