16.9 Black box for parameters

The application software logs all changes made to the unit parameters, recording the date and time of the change and indicating
the old value and the new one after the change. It also keeps a record of all the unit parameters, to offer an overview of the
status of the unit.
The file generated by the Parameters black box is encrypted and only readable using the "Service" software.
16.10 Maintenance signals
The software displays, in the same form as an Alarm / Signal event, the need to perform maintenance on the devices inside the
unit, i.e.:
fan;
compressors;
Heating element;
humidifier.
The signal is displayed when the set number of operating hours is exceeded. If the number of hours is equal to 0 (default value)
the maintenance signal for that device is disabled and therefore never appears.
The unit devices that certainly require periodic maintenance are the air filters and the humidifier. As regards the air filters, the
maintenance signal coincides with the ventilation signal, as the filter operating hours are the same as the fan operating hours.
After the signal is acknowledged, the counter can be reset and the hours start from zero.
Both the setting of the operating hour thresholds and the reset procedure are performed on the "Settings" menu, accessible
through the "Service" password.