Mitsubishi Electric Evolution+ s-MEXT Technical Manual page 72

Table of Contents

Advertisement

Mask of the terminal
LAN
--------------- P26.14
Delay before
protection OFF with
Treturn in range:
300s
LAN
--------------- P26.15
Delay bef. Protection
ON with Treturn
out of range:
060s
LAN
--------------- P26.16
Active Fan on Stand-by
units enable:
N
--------------- P26.17
Stand-by units Active
Fan speed:
070%
LAN
--------------- P26.18
Active Pressure Load
enable:
--------------- P26.19
Disable APL during
Diff.P probe alarm:
LAN
--------------- P26.20
H&L Local Pressure
protection enable:
LAN
--------------- P26.21
Diff. for ON with High
local DeltaP:
010Pa
--------------- P26.22
Diff. for ON with Low
local DeltaP:
010Pa
LAN
--------------- P26.23
Delay before
protection OFF with
local DeltaP in range:
300s
LAN
--------------- P26.24
Delay before
protection ON with
local DeltaP out of
range:
060s
Version 38
Parameter for configuring the time of deactivation of the Hot & Cold Spot function
after returning within the limits.
Visible only if Hot&Cold spot management is enabled.
Parameter for configuring the time of activation of the Hot & Cold Spot function after
exceeding the limits.
Visible only if Hot&Cold spot management is enabled.
Enable the Active Fan on Standby function.
Speed of the fans in units on standby.
Parameter enabling the Active Pressure Load function.
Visible only if LAN is enable and the fans are adjusted according to the air DeltaP.
N
Parameter for disabling fan regulation according to Active Pressure Load on units
with air differential transducer in alarm.
N
Visible if Active Pressure Load function is enabled.
Parameter for enabling the High & Low Local Pressure protection function.
N
Visible if Active Pressure Load function is enabled.
Parameters for setting the threshold for independent fan control on units with above-
average floor pressures.
Parameters for setting the threshold for independent fan control on units with below-
average floor pressures.
Visible only if high & low local pressure protection function is enabled.
Time before return to regulation according to the average pressure on units with
local pressure within the norm.
Visible only if high & low local pressure protection function is enabled.
Time before start of regulation according to local pressure on units with local
pressure outside the norm.
Visible only if high & low local pressure protection function is enabled.
Description
Par.N.
26.14
26.15
26.16
26.17
26.18
26.19
26.20
26.21
26.22
26.23
26.24
72