Example 4
Situation: "Perimeter" unit network split into two sections.
Units signalling the LAN disconnected alarm: 3 and 4.
Example 5
Situation: "Perimeter" unit network split into three sections.
Units signalling the LAN disconnected alarm: 2, 3, 4 and 5.
Example 6
Situation: "Perimeter" unit network split into two sections and unit 6 disconnected.
Units signalling the LAN disconnected alarm: 3, 4 and 6:

17.12.4 Consequences of the alarm

When a unit detects a disconnection on the local LAN network, the following occurs:
signal on the main mask;
forced unit activation in case it is in stand-by;
average regulation inhibited, in case it has been previously enabled;
Time count interruption for reserve unit rotation.
election of a new Priority if the network is divided into several sections.
Moreover, the Priority unit activates a backup unit.