17.8 Temperature and humidity average management

17.8.1

Introduction

When the units are connected to a LAN network, it is possible to leverage their connection to operate them according to the
average humidity and temperature value of all active units (that is, with active ventilation) not in the alarm status.
17.8.2

Average calculation

The average calculation is performed by all units in the same group only if the regulation based on the average value has been
enabled from the user terminal. To perform this calculation, all units in the same group share the ambient temperature and
humidity values read by their probes and calculate the average.
The average temperature and humidity consider only those units that:
they belong to the same group;
Are not in stand-by (in case the reserve unit rotation function is enabled);
Are not in alarm (see following chapters);
Are not off from user terminal.
The user terminal of each individual unit in the same group also displays the value read by its own temperature probe.
17.8.3

Enable the use of the averagne

Use of the average temperature and humidity value is only enabled if:
The function is enabled.
Faults in the LAN connection of the units belonging to the same group are not found.
If faults are detected in the LAN network, the unit immediately exits average based adjustment mode and only works based on
local values (i.e.: the values read by the unit probes).
The diagram below represents the operating mode described above
UNIT 3
UNIT 2
T adj: 23.5°C
MA S TER
UNIT 10
UNIT 9
Figure 17-5: chart illustrating adjustment according to the average temperature and humidity.
The parameters for enabling and configuring the average based adjustment mode are under the "LAN" menu, which can be
accessed by entering the "Service" password.
For the default values, see the parameters table.
Version 38
UNIT 4
UNIT 5
LAN
Adj. T.Average
UNIT 7
UNIT 8
U1 =
U2 =
T: 23,2°C
T: 24,2°C
U6 =
U7 =
UNIT 6
T: 22,9°C
T: 23,6°C
Unit Temperatures
U3 =
U4 =
U5 =
T: 23,8°C
T: 22,5°C
T: 24,0°C
U8 =
U9 =
U10 =
T: 24,6°C
T: 23,0°C
T: 22,9°C
203

Advertisement

Table of Contents
loading

Table of Contents