2.5.8

[P--] Default Menu

Accessible from: "Factory" group.
Mask of the terminal
Default
Default
Default Setup
N
Default
Reset History
of Alarms
N
Default
Connect KIPlink to the
WiFi network
CLIMA_WIFIeea
N
Verify the IP achieved
with specific wizard
tool
2.5.9

[P20] Regulations Menu

Accessible from: "Service" group.
Mask of the terminal
Regulations
Regulations
--------------- P20.01
Regulation probe
choice:
Return Temp
Regulations
--------------- P20.02
Fan start delay after
power-ON:
000s
Version 38
Access mask to the "Default" menu (initialisation of the factory parameters).
This restores the default values.
Wipes the memory and restores the default values of the parameters. The chiller
must then be programmed with the parameter set during factory testing.
The mask is not displayed when the chiller is ON.
Deletes the contents of the alarms log on the display.
It allows to start the test mode for the KIPlink.
Access mask to "Regulations" menu.
Type of temperature probe used for adjustment.
[Return | Delivery].
Visible only on chilled water units or direct expansion units with at least one
inverter compressor.
Fan start delay after power ON.