Mask of the terminal
Regulations
--------------- P20.24
Cooling setpoint
lower limit:
18.0°C
--------------- P20.25
Cooling setpoint
upper limit:
32.0°C
Regulations
--------------- P20.26
Heating setpoint
lower limit:
12.0°C
--------------- ------
Regulations
--------------- P20.28
Supply air temp. limit
function enable:
--------------- P20.29
Supply air temp.
limit:
10.0°C
Regulations
--------------- P20.44
Frost Protection funct
type:
By LP transd
Regulations
--------------- P20.47
LP setpoint for
frost protect.:07.5bar
--------------- P20.48
LP differential for
frost protect.: 1.0bar
Regulations
--------------- P20.49
Delay bef. Activating
frost protect.:
10min
Regulations
--------------- P20.50
Make Frost al. manual
rearm after count:
--------------- P20.51
Frost alarms count per
hour before manual:
Regulations
--------------- P20.53
Min Increase N.Zone
for Tsupply reg.:1.5°C
--------------- P20.54
Min Decrease N.Zone
for Tsupply reg.:1.5°C
Version 38
Cooling setpoint minimum limit.
Cooling setpoint maximum limit.
Heating setpoint minimum limit.
Hot water temperature minimum limit.
Parameter for configuring the limitation according to delivery air temperature.
N
Parameter for setting the Minimum delivery air temperature limit
Visible only if the delivery air temperature limitation function is enabled.
Enable the frost-free function protection.
Possible configurations: Disabled - From LP transducer.
Low pressure setpoint for activation of the Frost-Free function.
Low pressure differential for deactivation of the Frost-Free function.
Delay before activation of the Frost-Free function.
Enable switching from automatic to manual reset of the Frost-Free alarm after
counting.
Y
Maximum number of Frost-Free alarms in one hour before switching to manual
3
reset of the alarm.
Attention: if switching of the type of reset is disabled, the alarm is only in Manual
reset mode.
Minimum Neutral Switch-On Zone for increasing the resources for delivery air
control.
Minimum Neutral Switch-Off Zone for decreasing the resources for delivery air
control.
Visible only if the unit is adjusted according to the delivery air.
Description
Par.N.
20.24
20.25
20.26
20.28
20.29
20.44
20.47
20.48
20.49
20.50
20.51
20.53
20.54