Mask of the terminal
Config.
--------------- P10.53
Unit gas type:
R410A
Config.
--------------- P10.16
Diff. pressure probe
lower limit:
0000Pa
--------------- P10.17
Diff. pressure probe
upper limit:
0100Pa
Config.
--------------- P10.29
LP pressure probe
presence on main
board:
Config.
--------------- P10.52
LP Probe Type:
0-5Vrat
Config.
--------------- P10.30
LP pressure probe
lower limit:
00.0bar
--------------- P10.31
LP pressure probe
upper limit:
30.0bar
Config.
--------------- P10.20
Outdoor temperature
probe enable:
Config.
--------------- P10.22
Brand:
Evolution+
Config.
------------ P10.26-28
Unit serial number:
032000000
Version 38
Parameter for setting the type of gas used in direct expansion circuits
[R410A – R32].
Visible only on units with at least one direct expansion circuit.
Parameters for setting the Start scale value of the differential pressure
transducer.
Parameters for setting the End scale value of the differential pressure
transducer.
Visible only on units with deltap or air flow rate control.
Parameter for setting the presence of the low pressure transducer on
the base board.
Y
Parameter for setting the type of low pressure transducer (0:0-5Vrat,
1:4-20mA).
Visible only with the low pressure transducer on base board enabled.
Start scale value of low pressure transducer.
End scale value of low pressure transducer.
Visible only on units with low pressure transducer on base board.
External T probe enable.
N
Visible only on units without Direct Free Cooling.
Initial logo.
[Evolution+ | De' Longhi | ICS | Neutral | EATON | Mitsubishi RC ].
Setting of the unit serial number.
Description
Par.N.
10.53
10.16
10.17
10.29
10.52
10.30
10.31
10.20
10.22
10.26
10.27
10.28
46