[P12] Compressor Menu - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

2.5.4

[P12] Compressor Menu

Accessible from: "Factory" group.
Mask of the terminal
Compressor
Compressor
--------------- P12.01
Compressor
Minimum ON time:
180s
--------------- P12.02
Compressor
Minimum OFF time: 180s
Compressor
--------------- P12.03
Comp. Minimum ON-ON
time (same comp.):360s
----------------------
----------------------
Version 38
Access mask to "Compressor" menu.
Parameter for setting Minimum compressor ON time.
Parameter for setting Minimum compressor OFF time.
Visible only on units with at least one compressor.
Minimum time between two ONs (switching-ons) of the same compressor.
Value of the cooling ramp at which to start the inverter compressor.
Visible only on units with inverter compressor.
Description
Par.N.
12.01
12.02
12.03