Heating; Heating Resources; On/Off Heating Element Management - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

HEATING

6

6.1 Heating resources

The sources available for ambient air heating are the following:
Heating elements, managed as simple on/off loads.
INFORMATION:
The activation of the electric heaters forces the demand for ventilation at the maximum speed. This speed
is defined as the greater between P10.10 and that generated by the ventilation control logics.

6.2 On/off Heating element management

The parameter indicating the presence of on/off electric heaters is in the "Optional" menu, which can be accessed by
entering the "Service" password.
Electric heaters, when present, have two different power loads. Therefore, they are managed according to three heating steps,
as depicted in the diagram below.
The heating Setpoint parameter is in the "Setpoint" menu.
The heating differential parameter is in the "Regulations" menu, which can be accessed by entering the "Service" password.
For the default values, see the parameters table.
The association of the heaters with the steps reflects the "binary management":
Step 1: heaters 1.
Step 2: heaters 2.
Step 3: heaters 1 + heaters 2.
Activating the heating elements is possible only when all the following conditions are met:
Adjustment consent is active;
The heating element overheating alarm is not present (from thermostat);
the dirty filters signal is not present;
none of the compressors are in cooling mode;
Version 38
Step 3
Step 2
P50.02 -
2/3
P20.19
P20.19 Differential
Figure 6-1: chart showing the management of hot resources with one heater.
Step 1
P50.02 -
P50.02
T
ambient
1/3
P20.19
(°C)
143

Advertisement

Table of Contents
loading

Table of Contents