Mask of the terminal
Unit - Remote 1 T+H
30.2°C
53.0%
Status: Online
Unit - Remote 2 T+H
31.0°C
50.5%
Status: Online
Unit - Remote 3 T+H
29.9°C
52.2%
Status: Online
Unit - Remote 4 T+H
30.4°C
51.7%
Status: Online
Unit - External T+H
12.7°C
72.0%
Status: Online
Unit - Pressure Probes
09.3bar
09.4bar
Unit - Regulat. Ramps
Cooling:
073.2%
Heating:
000.0%
Post Heating: 000.0%
FC Damper:
100.0%
Unit - Internal Fan
Speed Request:
063%
Regulation Type:
Standard
Unit - Internal Fan
Speed Request: 063%
Regulation Type:
Standard
Current Speed (%):
Fan1:063.0 Fan2:063.0
Fan3:063.0 Fan4:000.0
Fan5:063.0 Fan6:063.0
Version 38
Mask that displays the value of the serial remote probe 1 (address 129).
Visible if at least one serial remote probe is configured
Mask that displays the value of the serial remote probe 2 (address 130).
Visible if at least two serial remote probes are configured
Mask that displays the value of the serial remote probe 3 (address 131).
Visible if at least three serial remote probes are configured
Mask that displays the value of the serial remote probe 4 (address 132).
Visible if at least four serial remote probes are configured
Mask that displays the value of the serial external probe (address 133).
Visible if the probe is configured.
Display of the values of the pressure probes.
Circuit 1 low pressure switch
Circuit 2 low pressure switch
Regulation ramp value reading.
Mask that displays the the demand value and type of ventilation regulation.
Visible only on units with EC fans controlled by an analog signal.
Mask that displays the the request value and type of ventilation regulation and
the actual speed of the fans.
Only the data of the fans actually installed in the unit are displayed.
Visible only on units with ec fans controlled via serial communication.
Description