[P10] Config. Menu

Accessible from: "Factory" group.
Mask of the terminal
Config.
Config
--------------- P10.33
Unit type:
Perimetral
- - - - - - - - - - -
Cold type set:
Direct Expansion
Config
--------------- P10.35
Amount of CW Circuits:
----------------------
----------------------
---------------------
Config
--------------- P10.36
Amount of DX Circuits:
Cold type set:DX
Config
-----------------10.54
Condensing unit type:
None/t-Mate
Cold type set:DX
Config
-----------------10.55
MIN time OFF Mr.SLIM:
120s
Cold type set:SM
Config
--------------- P10.10
Internal fan project
speed:
070%
Config.
--------------- P10.11
Maximum reduction of
fan project speed: 20%
Resulting Min speed:
070 – (070x 20%) = 056
Version 38
Access mask to Config. Menu. (Configuration).
Parameter for setting the type of unit.
[Perimetral | Rack Cooler | Cooling Door | Modular Perimetral | TLC]
Displays the type of cooling resources set.
Parameter for setting the number of chilled water circuits.
0
Parameter for setting the use of a chilled water circuit as an Indirect
Free Cooling circuit.
Displays the type of cooling resources set.
Parameter for setting the number of direct expansion circuits.
1
Displays the type of cooling resources set.
Parameter for setting the type of condensing unit.
[None/t-Mate | HCAT/i-HCAT | m-MOCU | Mr.Slim]
Visible only with at least one direct expansion circuit installed.
Minimum off time of Mr. Slim units.
Internal fan project speed.
Visible only on units with EC fans controlled by an analog signal.
Maximum reduction of the project speed (determines the minimum
project speed of the internal fan).
Description
Par.N.
10.33
10.35
10.36
10.54
10.55
10.10
10.11