Code
Display description
Event
Remote Temp. Probe2
122
Failed/Disconnected
Event
Remote Temp. Probe3
123
Failed/Disconnected
Event
Remote Temp. Probe4
124
Failed/Disconnected
Event
Ret T+H Humidity Probe
125
Failed/Disconnected
Event
Remote Humidity Probe
126
Failed/Disconnected
Event
Remote Humidity Probe2
127
Failed/Disconnected
Event
Remote Humidity Probe3
128
Failed/Disconnected
Event
Remote Humidity Probe4
129
Failed/Disconnected
Event
Diff. Pressure Probe
130
Failed/Disconnected
Event
Remote 2 Probe
131
Offline
Event
Remote 3 Probe
132
Offline
Event
Remote 4 Probe
133
Offline
Event
Supply Air T. Probe
140
Failed/Disconnected
Event
Return Temp. T+H Probe
141
Failed/Disconnected
Version 38
Details
Remote T+H probe 2 temperature sensor
A122
fault.
Visible only when the Remote T+H probe 2
is present.
Remote T+H probe 3 temperature sensor
A123
fault.
Visible only when the Remote T+H probe 3
is present.
Remote T+H probe 4 temperature sensor
A124
fault.
Visible only when the Remote T+H probe 4
is present.
Return T+H probe humidity sensor fault.
A125
Visible only when the Return T+H probe is
present.
Remote T+H probe humidity sensor fault.
A126
Visible only when the Remote T+H probe
is present.
Remote T+H probe 2 humidity sensor fault.
A127
Visible only when the Remote T+H probe 2
is present.
Remote T+H probe 3 humidity sensor fault.
A128
Visible only when the Remote T+H probe 3
is present.
Remote T+H probe 4 humidity sensor fault.
A129
Visible only when the Remote T+H probe 4
is present.
Air differential pressure probe fault.
A130
Visible only if capacity or air DeltaP control
is enabled.
Remote T+H probe 2 disconnection alarm
A131
(serial connection).
Visible only if the probe is enabled.
Remote T+H probe 3 disconnection alarm
A132
(serial connection).
Visible only if the probe is enabled.
Remote T+H probe 4 disconnection alarm
A133
(serial connection).
Visible only if the probe is enabled.
A140
Delivery air temperature probe fault.
Return T+H probe temperature sensor
A141
fault.
Visible only when the Return T+H probe is
present.
Event
Reset Time Position Action
Time
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
A
A
U
NO
NO
NO
FN
HU+
DH
NO
NO
NO
NO
FN
NO
NO
NO
FN
Lim
NO