[P27] Optional Menu - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

2.5.18

[P27] Optional Menu

Accessible from: "Service" group.
Mask of the terminal
Optional
Optional
--------------- P27.02
Electric heater
enable:
--------------- P27.03
Electric heater
type:
ON-OFF
Optional
--------------- P27.04
T+H return probe
(humidity sensor):
--------------- P27.05
Humidifier:
Disabled
Optional
--------------- P27.06
Humid. Cylinder type:
1 kg/h Reduct 200V
1-ph Drain Pump
Confirm change:
Type changed
Optional
--------------- P27.07
Max steam production:
100%
Optional
--------------- P27.16
Humidifier Periodical
Drain funct. Enable: N
--------------- P27.17
Delay between each
Periodical Drain: 024h
Optional
--------------- P27.18
Humidifier Inactivity
Drain funct. Enable: N
--------------- P27.19
Inactivity duration
before Drain:
03d
Optional
--------------- P27.09
Dehumidification
enable :
N
Version 38
Access mask to the "Optional" menu.
Enable the heating elements.
N
Heating elements type.
[ON/OFF].
Parameter for enabling the air return serial T/H probe.
N
Enable the humidifier and type.
[Disabled | Internal | External].
Parameter for selecting the humidifier cylinder.
Confirmation of the selected cylinder.
Y
VIsible only if the internal humidifier type is set.
Maximum steam production.
Visible only when the internal type of humidifier is set.
Enable the periodic discharge function during operation of the humidifier.
Hours of continuous operation between each instance of periodic discharge.
Visible only when the internal type of humidifier is set.
Enable the humidifier inactive discharge function.
Days of inactivity of the humidifier before discharge.
Visible only when the internal type of humidifier is set.
Dehumidifier configuration (N:disabled – Y:enabled).
Description
Par.N.
27.02
27.03
27.04
27.05
27.06
27.07
27.16
27.17
27.18
27.19
27.09
76