[P28] Regulations 2 Menu - Mitsubishi Electric Evolution+ s-MEXT Technical Manual

Table of Contents

Advertisement

2.5.19

[P28] Regulations 2 Menu

Accessible from: "Service" group.
Mask of the terminal
Regulations
2
Regulations 2
No Regulations 2
Parameters Available
Regulations 2
--------------- P28.18
Sup. Probes regulation
TH NTC1---------------
THr1 THr2 THr3 THr4
Param. Value:
00511
Regulations 2
--------------- P28.19
TH NTC1 --------------
THr1 THr2 THr3 THr4
Param. Value:
00511
Regulations 2
--------------- P28.20
Ret. Calculation type:
1
st
probe enabled
--------------- P28.21
Sup. Calculation type:
1
st
probe enabled
Regulations 2
--------------- P28.22
UV Lamp Activation:
Disabled
-----------------------
-----
Regulations 2
--------------- P28.30
Measurement system:
International
Version 38
Access mask to "Regulations 2" menu.
Mask displayed when none of the parameters of this menu for the unit are
available.
Parameter for indicating the temperature probes that will be used for the
calculation of the delivery air temperature.
Bit 0: NTC1 – Bit 1: TH -
Bit 5: THr1 – Bit 6: THr2 – Bit 7: THr3 – Bit 8: THr4
Parameter for indicating the temperature probes that will be used for the
calculation of the return air temperature.
Bit 0: NTC1 – Bit 1: TH -
Bit 5: THr1 – Bit 6: THr2 – Bit 7: THr3 – Bit 8: THr4
Parameter for setting the type of calculation of the return air temperature.
Parameter for setting the type of calculation of the delivery air temperature.
Parameter for choosing the type of UV lamp activation command.
[Disabled].
Parameter for switching the UV lamp on/off.
Visible only with UV lamp activation from keypad.
Imperial system enable [0: International metric system - 1: Imperial metric
system].
Description
Par.N.
28.18
28.19
28.20
28.21
28.22
28.30
79