Ground for the DC-Powered Distribution Unit
j58890r1 RBP 042296
Figure notes
DC power cabinet
1
2
DC Power Distribution Unit
Ground Discharge Bar
3
6 AWG (#40) (4 mm2) Wire
4
5
GRD Connector Terminal on DC-Powered Distribution Unit
To Additional DC-Powered Distribution Units (if required)
6
Connect DC Power Cabinet Ground
Cut a length of 6 AWG (#40) (4 mm
1
DISCHARGE bar on the DC power cabinet and the single-point ground block on the
expansion control media gateway A (bottom media gateway in
Gateway'' on page
2
At the DC power cabinet, connect the wire to the GROUND DISCHARGE bar.
Route the wire to expansion control media gateway A and connect to the single-point
3
ground block.
Repeat for each expansion control media gateway A in the S8700 Multi-Connect
4
configuration room.
2
) wire long enough to reach between the GROUND
110).
October 2002
Installing an Avaya SCC1 Media Gateway Stack
''Ground for Media
109