N5: Feed Forward Control; N6: Online Tuning; N7: Ez Drive - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

No.
Name
(Hex.)
n3-04
HSB Overload Time
(058B)
Expert
n3-13
OverexcitationBraking
(OEB) Gain
(0531)
n3-14
OEB High Frequency
Injection
(0532)
Expert
n3-21
HSB Current
Suppression Level
(0579)
n3-23
Overexcitation Braking
Operation
(057B)

n5: Feed Forward Control

No.
Name
(Hex.)
n5-01
Feed Forward Control
Selection
(05B0)
n5-02
Motor Inertia
Acceleration Time
(05B1)
n5-03
Feed Forward Control
Gain
(05B2)
n5-04
Speed Response
Frequency
(05B3)
RUN
Expert

n6: Online Tuning

No.
Name
(Hex.)
n6-01
Online Tuning Selection
(0570)
n6-05
Online Tuning Gain
(05C7)
Expert

n7: EZ Drive

No.
Name
(Hex.)
n7-01
Damping Gain for Low
Frequency
(3111)
Expert
n7-05
Response Gain for Load
Changes
(3115)
Expert
YASKAWA SIEPC71061753A GA500 Technical Manual
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time used to detect oL7 [High Slip Braking Overload], which occurs when the
output frequency does not change during high-slip braking. Usually it is not necessary
to change this parameter.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain value that the drive multiplies by the V/f pattern output value during
overexcitation deceleration to calculate the overexcitation level.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that injects harmonic signals during overexcitation deceleration.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the upper limit of the current that is suppressed at the time of overexcitation
deceleration as a percentage of the drive rated current.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the direction of motor rotation where the drive will enable overexcitation.
0 : Disabled
1 : Enabled Only when Rotating FWD
2 : Enabled Only when Rotating REV
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the feed forward function.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the length of time for the motor to accelerate from the stopped to the maximum
frequency with a single motor at the rated torque. Inertia Tuning automatically sets the
motor acceleration time.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the ratio between load inertia and motor inertia. Inertia Tuning automatically sets
the Feedforward Control Gain value.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the response frequency for the speed reference. Usually it is not necessary to
change this parameter.
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the type of motor data that Online Tuning uses for OLV control.
0 : Disabled
1 : Line-to-Line Resistance Tuning
2 : Voltage Correction Tuning
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the compensation gain when n6-01 = 2 [Online Tuning Selection = Voltage
Correction Tuning]. Usually it is not necessary to change this parameter.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the oscillation suppression gain for the low speed range.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the response gain related to changes in the load.
11.12 n: Special Adjustment
Default
Ref.
(Range)
40 s
714
(30 - 1200 s)
1.10
714
(1.00 - 1.40)
0
715
(0, 1)
100%
715
(0 - 150%)
0
715
(0 - 2)
Default
Ref.
(Range)
0
716
(0, 1)
Determined by C6-01,
716
E5-01, and o2-04
(0.001 - 10.000 s)
1.00
717
(0.00 - 100.00)
Determined by A1-02
717
(0.00 - 500.00 Hz)
Default
Ref.
(Range)
0
718
(0 - 2)
1.0
718
(0.1 - 50.0)
Default
Ref.
(Range)
1.0
718
(0.1 - 10.0)
50
718
(10 - 1000)
11
397

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga500 series

Table of Contents