Configuration
September 2020
Damping with AMS Device Manager
Procedure
1. Right select the device and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully read the warning and click Yes if it is safe to apply the changes.
Damping with a LOI
Reference
Figure 2-11: Damping with LOI
2.7

Configuring the LCD display

The LCD display configuration command allows customization of the LCD display to suit
application requirements. The LCD display will alternate between the selected items.
Pressure Units
% of Range
Scaled Variable
Sensor Temperature
mA/Vdc Output
In the following instructions, the LCD display can also be configured to display
configuration information during the device startup. Select Review Parameters at Startup
to enable or disable this functionality.
Reference
2.7.1
Configuring LCD display with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
24
Figure 2-11
to enter damping values using an LOI.
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Configuring the LCD display
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
with LOI for image of LCD display screen.
2, 2, 4
Rosemount 2051 Pressure Transmitter
Reference Manual