Alcatel-Lucent 1665 Installation Manual page 252

Data multiplexer (dmx)
Hide thumbs Also See for 1665:
Table of Contents

Advertisement

Operational tests
............................................................................................................................................................................................................................................................
This command creates a cross-connection to map 28 DS1s of a DS1circuit pack or the first
DS3 of a DS3/EC1 or TMUX circuit pack in a Function unit slot(s) to the first STS-1 of
the Main OLIUs.
........................................................................................................................................................................................................................
6
Select Configuration -> Alarms -> Alarm Severity Assignment Profile.
........................................................................................................................................................................................................................
7
After screen appears, click the "+" next to ASAP Type System, Highlight DEFAULT and
click the Provision Button.
........................................................................................................................................................................................................................
8
After the screen on the right appears, click on the Alarm Level on the Power/Fuse
Failure row and change the alarm severity to Major.
........................................................................................................................................................................................................................
9
Click APPLY.
........................................................................................................................................................................................................................
10
Unseat one of the LNW6/LNW7/LNW8, LNW16/LNW19/LNW19B or LNW18 circuit
packs from the function group being used.
Result:
Note:
time is 2 seconds.
........................................................................................................................................................................................................................
11
Press the ACO pushbutton on the SYSCTL.
Result:
The MN audible alarm clears.
........................................................................................................................................................................................................................
12
Using a small flat bladed screwdriver, set one of the circuit breakers to OFF.
Result:
........................................................................................................................................................................................................................
13
Press the ACO pushbutton on the SYSCTL.
Result:
The MJ audible alarm should clear.
............................................................................................................................................................................................................................................................
5 - 6
Activated office alarms: MN visual, MN audible.
Alarms will not be activated until the alarm delay time has passed. The default
Activated office alarm: MN visual.
Activated office alarms: MJ visual, MJ audible.
Activated office alarm: MJ visual.
Office alarm test
365-372-304R7.1
Issue 2 March 2008