Alcatel-Lucent 1665 Installation Manual page 196

Data multiplexer (dmx)
Hide thumbs Also See for 1665:
Table of Contents

Advertisement

Installation tests
............................................................................................................................................................................................................................................................
........................................................................................................................................................................................................................
8
Complete the above test on all Function unit slots terminating at DSX equipment. Once
you have completed the test make sure that all loopbacks have been removed at the
Customer Network Control Center before moving on to any other testing.
........................................................................................................................................................................................................................
9
Check off the appropriate box in
E
O
N D
........................................................................................................................................................
DS1 non-terminating equipment transmission testing (optical main OLIU)
Perform the following steps for all Alcatel-Lucent 1665 DMX shelf Function unit slots
that are cabled to a DSX-1 and not to any terminating equipment.
A Function unit slot cabled to the DSX-1 must contain a 28DS1 (LNW6 or LNW7) circuit
pack or a 56DS1/E1 (LNW8) circuit pack in order to perform these tests. If the Alcatel-
Lucent 1665 DMX shelf is not fully populated, it may be necessary to move the circuit
pack(s) from slot to slot in order to test all DS1 cabling.
This procedure requires the use of a DS1 test set.
Procedure
This command creates a cross-connect to map the first DS1 of a DS1 circuit pack in a
Function unit to the first VT1.5 within the first VT Group of STS1 of the Main OLIUs.
........................................................................................................................................................................................................................
1
Log on to the Alcatel-Lucent 1665 DMX shelf using the CIT software as described in the
3,
"Use of WaveStar
........................................................................................................................................................................................................................
2
Select Configuration -> Cross Connections...
........................................................................................................................................................................................................................
3
Use the Cross-Connection Wizard to enter a new cross-connection at the VT1.5 rate,
UPSR Ring Add/Drop, starting with m-1-1-1-1 and fn-1-1-1 (fn will be a,b,c or d
depending on the slot where the DS1 CP is located). Refer to
Connections" (p.
........................................................................................................................................................................................................................
4
Set the DS1 test set to transmit and receive a Quasi-Random Sequence Signal (QRSS)
with B8ZS formatting.
............................................................................................................................................................................................................................................................
4 - 1 2
S
F
T E P S
®
CIT software" (p.
4-19).
Appendix E, "Installation
3-9).
Local equipment and cross-connect tests
checklist".
Table 4-2, "DS1 Cross-
Issue 2 March 2008
365-372-304R7.1