Replacing The Electronics Module - Eaton BladeUPS User Manual

For use with eaton bladeups 5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Replacing the Electronics Module

You can easily replace the electronics module without turning the UPS off or disconnecting the load. Battery
mode is not available and your equipment is not protected; however, the utility power continues to be filtered
passively by the UPS.
If you prefer to remove input power to change the electronics module, see "Individual UPS Shutdown" on
page 102.
To replace the electronics module:
1.
Standalone UPS configurations only. Transfer the UPS to Bypass mode. Continue to Step 3.
Parallel for capacity configurations only. Transfer the UPS to Bypass mode. The CAN bus remains energized.
Parallel for redundancy configurations only. No mode transfer is necessary. If the UPS is operating in a
parallel for redundancy configuration when its electronics module is removed, the load automatically
transfers to the remaining UPSs. The CAN bus remains energized.
2.
Parallel configurations only. Disconnect the redundant signal cable(s) from the UPS. For the location of
the redundant signal cable, see Figure 64 on page 79.
3.
Remove the UPS front cover and the electronics module and set them aside (see Figure 85):
To remove the UPS front cover, grasp the fingergrips on both sides of the cover and pull the cover
l
forward firmly. Unplug the LCD cable connecting the back of the control panel to the electronics
module.
To remove the electronics module, remove the electronics module locking screw at the top left of the
l
electronics module and retain. Grasp the ring handle at the middle of the module and pull the module
slowly out of the cabinet. Pull firmly to unseat the connectors. Use two hands to support the module.
NOTE
DO NOT DISCONNECT the electronics module while the UPS is in Battery mode.
NOTE
In single unit and capacity parallel systems, disconnecting the control panel from
the electronics module automatically transfers the UPS to Bypass mode. However,
transferring the UPS to Bypass mode manually BEFORE disconnecting the control
panel provides extra protection to the electronics module and is recommended.
NOTE
Treat the electronics module with care to avoid damaging the fans, connectors, or
internal circuitry.
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality
UPS Maintenance
125

Advertisement

Table of Contents
loading

Table of Contents