Unpack the Powerware Hot Sync CAN Bridge Card and verify that the card was not damaged during
shipment (see Figure 61).
Figure 61. Powerware Hot Sync CAN Bridge Card
5.
If there is a Jumper J7 on the Powerware Hot Sync CAN Bridge Card, remove and discard (see Figure 68
on page 86).
NOTE
Eaton recommends installing the Powerware Hot Sync CAN Bridge Card in
X-Slot Communication Bay 2 (see Figure 60 on page 74), leaving Communication
Bay 1 available for other types of X-Slot cards.
6.
Remove the X-Slot communication bay cover on the UPS and retain the screws.
7 .
Install the Powerware Hot Sync CAN Bridge Card into the open X-Slot communication bay #2 on the UPS
rear panel. Reinstall screws and tighten.
8.
Repeat Step 4 through Step 7 to install a CAN Bridge Card in each UPS to be paralleled.
NOTE
The BladeUPS parallel system can automatically assign identities to each UPS in the
system based on the order in which their CAN Bridge Cards are wired in Step 9
through Step 12. For more information, see "Auto-Identification" on page 117.
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality
Standard System Installation
76