Eaton BladeUPS User Manual page 136

For use with eaton bladeups 5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Table 18. Troubleshooting Alarms and Conditions
Alarm or Condition
ON BATTERY
Yellow
LED is on.
One short beep every five seconds.
BATTERY LOW
Yellow
LED is on.
Con tinuous beep for ten seconds.
BATTERY BREAKER
Red
LED is on.
One beep every three seconds.
ON BYPASS
Yellow
LED is on.
One beep every three seconds.
BYPASS UNAVAILABLE
Yellow
LED is flashing slowly.
One beep every second.
BATTERY CONNECTION
Red
LED is on.
One beep every three seconds.
OVERLOAD
Red
LED is on.
One beep every three seconds.
Possible Cause
A utility failure has occurred and the UPS is
in Battery mode.
The UPS is in Battery mode and the battery
is running low.
The UPS does not recognize the internal
batteries.
The UPS is in Bypass mode.
Bypass is not available because the UPS
may be receiving bypass utility power that
may be unstable or in brownout conditions.
The UPS does not recognize the internal
batteries.
Two or more battery trays are disconnected.
Power requirements exceed the UPS
capacity (greater than 100% of nominal; see
Table 24 on page 137 for specific output
overload ranges).
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality
Service and Troubleshooting
Action
The UPS is powering the equipment with battery power. Prepare your
equipment for shutdown.
This warning is approximate, and the actual time to shutdown may
vary significantly. Depending on the UPS load and number of
Extended Battery Modules (EBMs), the Battery Low warning may
occur before the batteries reach 25% capacity. See Table 27 on
page 138 for estimated runtimes and "Setting the Battery Low Alarm
Level" on page 104 for configuration information.
hen utility power is restored, the UPS restarts automatically,
provides power to the load, and charges the battery.
Verify that the UPS battery circuit breaker is in the ON (|) position. If
the condition persists, contact your service representative.
The equipment transferred to bypass utility power. Battery mode is
not available and your equipment is not protected; however, the
utility power continues to be passively filtered by the UPS. Check for
one of the following alarms: overtemperature, overload, UPS failure,
hot swap, or remote emergency power-off (REPO).
Check the bypass utility. The UPS continues to supply power to your
equipment. Check for one of the following alarms: bypass over or
under voltage, bypass over or under frequency, or bypass unavailable.
If the condition persists, contact your service representative.
Verify that all battery trays are fully seated and locked in place. If the
condition persists, contact your service representative.
Remove some of the equipment from the UPS. The UPS continues to
operate, but may switch to Bypass mode if the load does not
decrease. The alarm resets when the condition becomes inactive.
132

Advertisement

Table of Contents
loading

Table of Contents