Eaton BladeUPS User Manual page 142

For use with eaton bladeups 5 kva to 60 kva (n+1) systems
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

Table 25. Environmental and Safety
Relative Humidity
Operating Altitude
Transit Altitude
Heat Dissipation
Audible Noise
Leakage Current
Communication
Table 26. Battery
UPS Internal
Configuration
(40) 12V, 5 Ah
(20) 12V, 5Ah
Type
Monitoring
Charging (in minutes)
NOTE
Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load discharge.
Table 27. Standalone UPS Battery Runtimes at Full/Half Load (in Minutes)
Model
kW
BladeUPS 12
12/6
BladeUPS 12i
12/6
BladeUPS 8
8/4
BladeUPS 5.1
5.1/2.55
Single battery string
BladeUPS 5.1
5.1/2.55
Two battery strings
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
Table 28. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes at Capacity)
Number of UPSs
kW
2
24/12
3
36/18
NOTE
Battery times are approximate and vary depending on the load configuration and battery charge.
BladeUPS 12 Model
up to 2,000 meters (6,600 ft) with 1% derating per +100 meters (330 ft)
Batteries
+1 EBM
(20) 12V, 9 Ah
(5.1 k
only)
Advanced monitoring for earlier failure detection and warning
UPS Internal
Batteries
4.7/13.6
4.7/13.6
8.7/23
5.9/16.1
18.1/35.6
UPS Internal
Batteries
4.7/13.6
4.7/13.6
Eaton BladeUPS 5.1 kVA to 60 kVA (N+1) User's Guide 164201649—Rev 9 www.eaton.com/powerquality
BladeUPS 12i Model
Operating: 5–95% noncondensing
Non-operating: 5–95% relative humidity, 38.7°C (101.7°F)
Maximum wet bulb temperature with no cosmetic damage
Up to 1,000 meters (3,300 ft) above sea level;
Up to 15,000 meters (49,000 ft) above sea level
1432 BTU/hr maximum at 100% rated load (High Efficiency mode)
4094 BTU/hr maximum at 100% rated load (Standard mode)
Less than 58 dBA at 1 meter typical (Normal mode)
Less than 64 dBA at 1 meter typical (Battery mode)
<3.5 mA
DB-9: 1200–19200 baud
+2 EBMs
(40) 12V, 9 Ah
Sealed, maintenance-free, valve-regulated, lead-acid
8–10 times the discharge time
+1 EBM
+2 EBMs
9.5/27
17/42
9.5/27
17/42
17.7/41.5
27.9/65.5
21.7/45.8
37.2/80.1
32.1/66.3
48.1/101.6
+1 EBM
+2 EBMs
9.5/27
17/42
9.5/27
17/42
BladeUPS 8 Model
BladeUPS 5.1 Model
+3 EBMs
(60) 12V, 9 Ah
+3 EBMs
27/60
27/60
43.0/94.1
59.2/128
71.8/ 53.4
+3 EBMs
27/60
27/60
Specifications
+4 EBMs
(80) 12V, 9 Ah
+4 EBMs
34/76
34/76
54.7/120
79.0/175
91.1/198.0
+4 EBMs
34/76
34/76
138